Industry Buying is India's largest marketplace for Industrial Goods, Business Supplies, MRO Products, Tools, Equipment and many more. Wholesale Price, 7 Days Return, COD.
Shop By Category
View
View
View
View
Type of Product | contactor |
Model No | LC1D80AN7 |
Auxiliary Contacts | 1 NO + 1 NC |
Country of Origin | India |
Type of Product |
contactor |
Model No |
LC1D80AN7 |
Auxiliary Contacts |
1 NO + 1 NC |
Country of Origin |
India |
Application |
Motor control, Resistive load |
Series |
TeSys |
Pole |
3 |
Standard |
EN/IEC 60947-4-1, EN/IEC 60947-5-1, UL 60947-4-1, CSA C22.2 No 60947-4-1, IEC 60335-1 |
Average Impedance |
1.5 mOhm - Ith 80 A 50 Hz for power circuit |
Mechanical Durability |
6 Mcycles |
Device Short Name |
LC1D |
Mounting Support |
Rail, Plate |
Protection |
IP20 front face conforming to IEC 60529 |
Heat Dissipation |
4…5 W at 50/60 Hz |
Tightening Torque |
Control circuit: 1.7 N.m - on screw clamp terminals - with screwdriver flat Ø 6 mm, Control circuit: 1.7 N.m - on screw clamp terminals - with screwdriver Philips No 2, Power circuit: 8 N.m - on EverLink BTR screw connectors - cable 25…35 mm² hexagonal screw head 4 mm, Power circuit: 5 N.m - on EverLink BTR screw connectors - cable 1…25 mm² hexagonal screw head 4 mm, Control circuit: 1.7 N.m - on screw clamp terminals - with screwdriver pozidriv No 2, Power circuit: 2.5 N.m - on screw clamp terminals - with screwdriver pozidriv No 2 |
Height |
122 mm |
Width |
55 mm |
Insulation Resistance |
> 10 MOhm for signalling circuit |
Control Circuit |
AC at 50/60 Hz |
Fire Resistance |
850 °C conforming to IEC 60695-2-1 |
Rated Breaking Capacity |
1000 A at 440 V |
Certification |
CCC, CSA, EAC, UL, KC, DNV-GL, LROS (Lloyds register of shipping) |
Compatibility Code |
LC1D |
Power Dissipation Per Pole |
9.6 W AC-1, 6.3 W AC-3, 6.3 W AC-3e |
Product Range |
TeSys Deca |
Operating Time |
4...19 ms opening, 12...26 ms closing |
Coil Technology |
Without built-in suppressor module |
Protective Treatment |
TH conforming to IEC 60068-2-30 |
Over Voltage Category |
III |
Product or component Type |
Contactor |
Rated Insulation Voltage (Ui) |
Signalling circuit: 690 V conforming to IEC 60947-1, Power circuit: 690 V conforming to IEC 60947-4-1 |
Fuse Rating |
10 A gG for signalling circuit conforming to IEC 60947-5-1, 125 A gG at <= 690 V coordination type 1 for power circuit, 125 A gG at <= 690 V coordination type 2 for power circuit |
Rated Operational Voltage (Ue) |
690 V AC 25...400 Hz, 300 V DC |
Control Circuit Voltage Limits |
0.3...0.6 Uc (-40…70 °C):drop-out AC 50/60 Hz, 0.8...1.1 Uc (-40…60 °C):operational AC 50 Hz, 0.85...1.1 Uc (-40…60 °C):operational AC 60 Hz, 1...1.1 Uc (60…70 °C):operational AC 50/60 Hz |
Pole Contact Composition |
3 NO |
Utilisation Category |
AC-1, AC-4, AC-3, AC-3e |
Maximum Operating Rate |
3600 cyc/h 60 °C |
Depth |
120 mm |
Net Weight |
0.86 kg |
Motor Power (HP) |
5 hp at 115 V AC 60 Hz for 1 phase motors, 10 hp at 230/240 V AC 60 Hz for 1 phase motors, 20 hp at 200/208 V AC 60 Hz for 3 phases motors, 20 hp at 230/240 V AC 60 Hz for 3 phases motors, 40 hp at 460/480 V AC 60 Hz for 3 phases motors, 50 hp at 575/600 V AC 60 Hz for 3 phases motors |
Motor Power (KW) |
22 kW at 220...230 V AC 50/60 Hz (AC-3), 37 kW at 380...400 V AC 50/60 Hz (AC-3), 37 kW at 415 V AC 50/60 Hz (AC-3), 37 kW at 440 V AC 50/60 Hz (AC-3), 37 kW at 500 V AC 50/60 Hz (AC-3), 37 kW at 660...690 V AC 50/60 Hz (AC-3), 22 kW at 220...230 V AC 50/60 Hz (AC-3e), 37 kW at 380...400 V AC 50/60 Hz (AC-3e), 37 kW at 415 V AC 50/60 Hz (AC-3e), 37 kW at 440 V AC 50/60 Hz (AC-3e), 37 kW at 500 V AC 50/60 Hz (AC-3e), 37 kW at 660...690 V AC 50/60 Hz (AC-3e) |
Pollution degree |
3 |
Electrical Durability |
0.7 Mcycles 80 A AC-1 at Ue <= 440 V, 1 Mcycles 66 A AC-3 at Ue <= 440 V, 1 Mcycles 66 A AC-3e at Ue <= 440 V |
Minimum Switching Current |
5 mA for signalling circuit |
Minimum Switching Voltage |
17 V for signalling circuit |
Flame Retardance |
V1 conforming to UL 94 |
Compatibility |
M2 |
Signal Frequency |
25...400 Hz |
Protective Cover |
With |
Non-Overlap Time |
1.5 ms on de-energisation between NC and NO contact, 1.5 ms on energisation between NC and NO contact |
Safety Reliability Level |
B10d = 1369863 cycles contactor with nominal load conforming to EN/ISO 13849-1, B10d = 20000000 cycles contactor with mechanical load conforming to EN/ISO 13849-1 |
Operating Altitude |
0...3000 m |
Name of Manufacturer/Packer/Importer |
Schneider Electric |